---
title: "Switchboard Sizing Calculator: LV Switchboard Dimensions, Bays & Form of Separation to AS/NZS 61439"
url: "https://elecas.com.au/calculator/switchboard-sizing"
description: "Free switchboard sizing calculator: LV switchboard width, height, depth, bays and Form of separation to AS/NZS 61439, built from your functional sections."
updated: "2026-09-21"
standards:
  - "AS/NZS 61439.1:2016 (Low-voltage switchgear and controlgear assemblies: General rules)"
  - "AS/NZS 61439.2:2016 (Low-voltage switchgear and controlgear assemblies: Power switchgear and controlgear assemblies, including Forms of internal separation 1–4)"
  - "IEC 61439-2 (Low-voltage switchgear and controlgear assemblies: Power switchgear and controlgear assemblies)"
  - "AS/NZS 3000:2018 (Wiring Rules: switchboard construction, clearances and access requirements)"
author: "Wisam Tozah (B.Eng (Electrical), MIEAust, CPEng, NER, NSW DBP, NSW PRE, APEC, IntPE(Aus))"
site: "Elecas"
license: "https://elecas.com.au/terms"
usage: "Cite and link. Do not reproduce or train on this content."
---

# Switchboard Sizing Calculator: LV Switchboard Dimensions, Bays & Form of Separation to AS/NZS 61439

Source: https://elecas.com.au/calculator/switchboard-sizing

Free, browser-based switchboard sizing calculator for Australian and New Zealand electrical engineers, switchboard designers and builders. It estimates the physical footprint of a free-standing low-voltage switchboard assembly (overall width, height and depth in millimetres and the number of bays) directly from your functional sections. Enter the switchboard rating, the incoming and metering arrangement (main switch / incomer, CT metering chamber, MEN link, surge protection), the outgoing distribution and feeder sections, a spare-capacity allowance, the IP rating and cable-entry arrangement, and the Form of separation (Form 1 through Form 4b to AS/NZS 61439.2 / IEC 61439-2). The calculator builds the width by stacking the functional sections into standard bays (incoming switchgear, metering, distribution chassis, outgoing feeder cubicles, spare capacity and any optional bays) takes the height from the rating envelope or the height you enter, capped at the 2200 mm operator-reach limit, and takes the depth as the greatest of the rating-band envelope, the actual switchgear compartment depth and the IP-rating depth floor, plus a rear alley where the board is rear-connected. The Form of separation is recorded as a verified-assembly constraint rather than a generic width or depth adder, because its external dimensional effect depends on the manufacturer's tested internal arrangement. It returns a live board width, bay count and elevation sketch you can use for early space planning, switchroom and riser allocation, tender allowances and coordination: before the manufacturer confirms the verified assembly. Outputs are preliminary functional-section estimates for early design, not a final enclosure specification: AS/NZS 61439 does not prescribe a universal enclosure-size formula, so final busbar, terminal, thermal, clearance and enclosure dimensions must come from the manufacturer's verified assembly system before construction.

The Elecas Switchboard Sizing Calculator estimates the preliminary physical dimensions (width, height and depth in millimetres) and bay count of a free-standing low-voltage switchboard assembly from its functional sections (incoming switchgear, metering, distribution chassis, outgoing feeders and spare capacity) to support early-stage space planning under AS/NZS 61439. The selected Form of internal separation is carried as a verified-assembly constraint on the result rather than as a dimensional adder. It is a free browser-based early-design estimator and does not replace a manufacturer's verified assembly (design verification) to AS/NZS 61439.

## Key facts

- AS/NZS 61439 has no universal enclosure-size formula; final switchboard dimensions must come from the manufacturer's verified assembly.
- The calculator builds a preliminary width from functional sections: incomer, metering, distribution chassis, feeders and spare capacity.
- Higher Forms of separation (Form 3b, Form 4b) need more internal space in practice, but the increase is specific to the manufacturer's tested system, so the calculator records the Form as a constraint instead of applying a generic dimensional adder.
- Board depth follows the greatest of the rating envelope, the switchgear compartment depth and the IP-rating depth floor, plus a rear alley for rear-connected boards.
- A 20-25% spare-capacity allowance is the common convention for new switchboards.
- Beside the footprint the calculator reads the ratings an assembly declares under AS/NZS 61439: the product part (61439.2 or 61439.3), the Table 7 peak withstand for the entered fault level, the Table 101 assumed loading factor, the least Annex N copper bar for the main rating, and the impulse withstand, clearance, creepage and dielectric test voltage of Tables G.1, 1, 2 and 8.
- An assembly with a short-circuit rating not exceeding 10 kA, or protected by a current-limiting device cutting off at 17 kA or less, is exempt from short-circuit withstand verification (AS/NZS 61439.1 Clause 10.11.2).

## Who this page is for

Electrical engineers, switchboard designers, switchboard builders and manufacturers, electrical contractors and estimators who need an early-stage switchboard footprint (width, height, depth and bays) for space allocation, switchroom and riser planning, tender allowances and coordination on Australian and New Zealand low-voltage installations.

## Relevant standards

- AS/NZS 61439.1:2016 (Low-voltage switchgear and controlgear assemblies: General rules)
- AS/NZS 61439.2:2016 (Low-voltage switchgear and controlgear assemblies: Power switchgear and controlgear assemblies, including Forms of internal separation 1–4)
- IEC 61439-2 (Low-voltage switchgear and controlgear assemblies: Power switchgear and controlgear assemblies)
- AS/NZS 3000:2018 (Wiring Rules: switchboard construction, clearances and access requirements)

## What this tool does

- Estimate the overall width, height and depth of a free-standing LV switchboard in millimetres from your functional sections, for early space planning and tender allowances.
- Build the width from the incoming switchgear, metering (CT chamber, MEN link, surge protection), distribution chassis, outgoing feeder sections and spare-capacity allowance.
- Record the AS/NZS 61439.2 / IEC 61439-2 Form of separation (Form 1, 2a/2b, 3a/3b, 4a/4b) against the estimate as a verified-assembly constraint: no generic width or depth adder is invented, because the external dimensional effect of a Form depends on the manufacturer's tested internal arrangement.
- Size the depth from the greatest of the rating-band envelope, the actual switchgear compartment depth and the IP-rating depth floor (IP40 through IP66), with a rear alley added automatically for rear-connected boards.
- Add a spare-capacity percentage that expands both the chassis design ways and the reserved feeder space so the board has room to grow, plus discrete spare bays for future sections.
- See a live bay count and elevation sketch that updates as you change the rating, sections and Form.
- Understand up front that the result is a preliminary functional-section estimate for concept design: AS/NZS 61439 has no universal enclosure-size formula, so final dimensions must come from the manufacturer's verified assembly.

## How to estimate a switchboard size with the Elecas Switchboard Sizing Calculator

1. **Set the switchboard rating** — Choose the main switchboard rating (in amps) for the free-standing 3-phase assembly. The incoming main switch / incomer device is inferred from the rating, and the rating also selects the preliminary height and depth envelope the board is planned inside.
2. **Choose the Form of separation** — Select the AS/NZS 61439.2 / IEC 61439-2 Form of internal separation (Form 1, 2a/2b, 3a/3b or 4a/4b). The selection is recorded against every section and in the design notes as a verified-assembly constraint; it does not apply a generic width or depth increment, because the space a Form costs is specific to the manufacturer's tested cubicle system.
3. **Add the incoming and metering items** — Pick the incoming and metering sections that apply: CT metering chamber, MEN link section, surge protection. Each is added to the board width as its own functional section.
4. **Enter the distribution and feeder sections** — Add the outgoing distribution sections and their items. Final subcircuits are converted into chassis ways; larger outgoing ways are given dedicated feeder space.
5. **Set the spare capacity** — Choose a spare-capacity percentage (commonly around 20–25%). It is applied to both the chassis ways and the feeder space so the footprint already includes room to grow.
6. **Enter the design basis** — Enter the maximum demand and the prospective fault level at the board, and say who operates it. The demand is checked against the main rating, the fault level sets the Icw band and the Table 7 peak withstand, and the operator decides whether the board is a 61439.3 distribution board or a 61439.2 power switchgear assembly.
7. **Read the dimensions, bays and elevation** — Review the live overall width, the conservative height and depth, the bay count and the elevation sketch. Use them to reserve switchroom space, size the riser and set a tender allowance.
8. **Confirm with the manufacturer before construction** — Treat the result as a preliminary estimate. Before construction, confirm the final busbar, terminal, thermal, clearance and enclosure dimensions with the switchboard builder's verified assembly system to AS/NZS 61439.

## How switchboard sizing works: estimating LV switchboard dimensions to AS/NZS 61439

### What the switchboard sizing calculator actually estimates

The Elecas Switchboard Sizing Calculator produces a preliminary physical footprint for a free-standing low-voltage switchboard assembly: the overall width, height and depth in millimetres, the number of bays, and the layout implied by the chosen Form of separation. It is a concept-stage space-planning tool: you use it to reserve floor area in a switchroom, size a riser, set a tender allowance and coordinate the board with the architecture long before the switchboard builder confirms the final assembly.

What it deliberately does not do is invent a precise enclosure. AS/NZS 61439 is a performance and verification standard, not a dimensional catalogue: it does not publish a universal formula that turns a load schedule into an exact enclosure size. The real dimensions come out of a manufacturer's verified assembly system, where busbar bracing, terminal space, thermal rise, minimum clearances and the chosen switchgear range all interact. This calculator gives you a defensible early number; the verified assembly gives you the built one.

### How the width is built up from functional sections

Switchboard width is the dimension that actually scales with the design, so it is built up section by section. The calculator starts with the incoming switchgear (the main switch or incomer inferred from the switchboard rating), adds the metering arrangement you select (a CT metering chamber, the MEN link section and any surge-protection allowance) then adds the distribution chassis that carries the outgoing final subcircuits, and finally the dedicated feeder sections for larger outgoing ways.

Outgoing final subcircuits are converted into chassis ways, and larger outgoing items are given feeder space. The total width is the sum of these functional sections, packed into standard bays, which is why the result is reported both as an overall millimetre width and as a bay count with an elevation sketch. Because the width tracks the sections you enter rather than circuit names, adding metering, more feeders or a higher spare allowance visibly widens the board.

### Form of separation and how the calculator treats it

The Form of separation describes how far the internal barriers go in segregating busbars, functional units and terminals from one another, as set out in AS/NZS 61439.2 Table 104: Form 1 has no internal separation; Form 2 separates the busbars from all functional units, with the terminals for external conductors not separated from the busbars (2a) or separated from them (2b); Form 3 also separates the functional units from one another and the terminals from the units, again with the terminals not separated from the busbars (3a) or the terminals and external conductors separated from the busbars (3b); Form 4 separates every unit's terminals from every other unit as well, with the terminals in the same compartment as their unit (4a) or in their own separate compartments (4b). Australia and New Zealand add a construction suffix (Appendix ZZ 8.101.1): h where a device's integral housing provides the separation, i where insulation does, ih for both, so a board can be specified as Form 3bh or 3bi.

Higher Forms do cost space in practice: but how much depends entirely on the manufacturer's tested cubicle system, because the barriers are achieved inside a verified assembly rather than by a universal external increment. Rather than invent millimetres it cannot justify, the calculator records the selected Form as a verified-assembly constraint on the estimate and reports it on every section and in the design notes, without applying a generic width or depth adder. Choose the Form early (often Form 3b or Form 4b for main switchboards where maintenance on one circuit must be possible without isolating the whole board), and confirm its dimensional effect against the switchboard builder's range, because that is the only place the real number exists.

### How the height and depth are derived

Unlike width, the height and depth of a switchboard do not scale smoothly with the number of circuits: they step with the switchgear range, the busbar system and the cable-entry strategy. Height is therefore an envelope rather than a sum: the calculator starts from the preliminary assembly height for the selected main rating (or the board height you enter), caps it at the 2200 mm operator-reach limit, and packs the functional sections into the usable stack height inside that envelope. When a column of sections will not fit the usable height, the board grows sideways into another bay instead of growing taller.

Depth is taken as the greatest of four requirements rather than a single figure: the depth band for the selected main rating, the actual depth of the incoming switchgear compartment (an ACB board is deeper than an MCCB or switch-fuse board of the same rating), the depth floor implied by the selected IP rating, and any minimum depth you specify yourself. A rear-connected board then adds a rear alley on top of that front-connected depth, and the result is rounded up to the nearest 50 mm. Treat the returned height and depth as a safe box to plan around, then refine them against the manufacturer's selected range once the design firms up.

### Spare capacity: designing room to grow

Most switchboards are specified with spare capacity so future circuits can be added without a new board. The calculator takes a spare-capacity percentage and applies it to both the chassis ways (spare pole positions on the distribution chassis) and the feeder space (room for additional outgoing feeder sections), so the width you see already includes the growth allowance.

A common convention is around 20–25% spare, but the right figure depends on the client brief and how likely the installation is to expand. Setting it explicitly means the early footprint you reserve in the switchroom already carries the spare, rather than discovering at construction that there is nowhere to add the next circuit.

### Why this is a preliminary estimate, not a verified assembly

AS/NZS 61439.1 and 61439.2 require that a low-voltage assembly be demonstrated to comply through design verification (by testing, by calculation/comparison with a tested reference design, or by satisfying design rules) and routine verification of each built assembly. Dimensions are an outcome of that process, not an input you can compute in isolation: the same load schedule can fit different enclosure sizes depending on the manufacturer's tested system, busbar ratings and temperature-rise results.

That is why every result in this tool is labelled a preliminary functional-section estimate for early design, and why the final busbar, terminal, thermal, clearance and enclosure dimensions must come from the manufacturer's verified assembly system before construction. Use the calculator to plan space and price a tender with confidence; confirm the built board with the switchboard builder.

### The ratings an assembly declares, and where the calculator reads them

AS/NZS 61439.1 Clause 5 lists what an assembly manufacturer has to declare, and several of those figures can be read directly from the design basis entered here. The prospective fault level sets the rated short-time withstand current Icw (Clause 5.3.4) and, through Table 7, the rated peak withstand current Ipk (Clause 5.3.3): the r.m.s. fault is multiplied by n, 1.5 up to 5 kA, 1.7 to 10 kA, 2.0 to 20 kA, 2.1 to 50 kA and 2.2 above, so a 25 kA fault means a 52.5 kA peak that the busbar supports must hold. Clause 9.3.2 lets a rating declared for one duration be restated for another with I squared t constant up to 3 s, which is how the 1 s band is shown for 0.2 s and 3 s as well. Clause 10.11.2 exempts an assembly whose rating does not exceed 10 kA, or a circuit behind a current-limiting device with a cut-off of 17 kA or less, from short-circuit withstand verification; everything else must be verified by test or by comparison with a tested reference design.

The main rating is read against Annex N Table N.1, the operating current of bare copper bars at 55 degrees enclosure air and 70 degrees conductor, to suggest the least copper that carries it, one bar per phase before two, with the Annex N loss formula giving the watts per metre the bar dissipates. A bar the manufacturer has verified by test may be smaller, and a hotter enclosure needs more (Table N.2). Table 12 names the bar arrangement a rating band is type-tested with, from two 30 by 5 mm bars above 400 A to four 100 by 10 mm bars at 4000 A. Table 101 of the applicable part gives the assumed loading of the outgoing circuits when actual currents are not agreed: 0.9 for two or three circuits down to 0.6 for ten or more in a power switchgear assembly, one step lower in a distribution board for ordinary persons. And for a 230/400 V system the insulation figures follow: Table G.1 puts a main switchboard at the origin of the installation in overvoltage category IV at 6 kV impulse withstand and a distribution board at category III at 4 kV; Table 1 turns those into 5.5 mm and 3 mm minimum clearances, times 1.5 when verified by measurement rather than by impulse test; Table 2 gives 6.3 mm creepage at 400 V for pollution degree 3 and material group IIIa; Table 8 sets the 1890 V dielectric test.

Which part applies is decided by the scope of AS/NZS 61439.3: a board operated by ordinary persons, rated up to 250 A, with outgoing circuits up to 125 A and no more than 300 V to earth, is a distribution board (DBO) to Part 3; anything larger, or anything in a switchroom operated by skilled persons, is a power switchgear and controlgear assembly (PSC) to Part 2. The parts differ in the assumed loading table, in the neutral rule (Part 3 in Australia and New Zealand rates the neutral at 100 % of the board rating with single-pole devices only and 50 % with multi-pole devices) and in the minimum overvoltage category, which is III for a DBO.

### Standards reference set and how the tool uses them

AS/NZS 61439.1:2016 sets the general rules for low-voltage switchgear and controlgear assemblies: ratings, temperature rise, short-circuit withstand and the verification framework. AS/NZS 61439.2:2016 (aligned with IEC 61439-2) covers power switchgear and controlgear assemblies specifically and defines the Forms of internal separation (Form 1 to Form 4) that drive the internal space allowances in this calculator.

AS/NZS 3000:2018 (the Wiring Rules) governs how the switchboard is installed and accessed (construction, clearances, working space and main-switch/MEN requirements), which is why the calculator handles the incomer, MEN link and metering as distinct functional sections. The switchboard rating and outgoing schedule you enter typically come from an AS/NZS 3000 maximum-demand assessment and AS/NZS 3008.1.1 cable sizing, so the Elecas Maximum Demand and Cable Size calculators feed naturally into this one.

## Key terms

- **Functional unit** — A part of an assembly that performs one function (an incomer, an outgoing feeder or a final-subcircuit way) together with the switchgear and terminals belonging to it. AS/NZS 61439 sizes and separates an assembly by its functional units, which is why this calculator builds the board width from functional sections rather than from a circuit count.
- **Form of internal separation** — The degree to which an assembly's busbars, functional units and terminals are segregated by internal barriers, defined in AS/NZS 61439.2 Table 104: Form 1 (none), Form 2a/2b (busbars separated from the units, terminals not separated / separated from the busbars), Form 3a/3b (units also separated from one another, terminals not separated / separated from the busbars) and Form 4a/4b (each unit's terminals separated from every other unit, in the unit's compartment / in their own compartments). AS/NZS 61439.2 Appendix ZZ adds the suffixes h, i and ih for separation by a device housing, by insulation or both.
- **Rated peak withstand current (Ipk)** — The peak value of short-circuit current an assembly can withstand mechanically, which must be at least the peak of the prospective fault (AS/NZS 61439.1 Clause 5.3.3). It is the r.m.s. fault times the factor n of Table 7: 1.5 up to 5 kA, 1.7 to 10 kA, 2.0 to 20 kA, 2.1 to 50 kA and 2.2 above.
- **Rated short-time withstand current (Icw)** — The r.m.s. short-circuit current an assembly can carry for a stated time, usually 1 s, without damage (AS/NZS 61439.1 Clause 5.3.4). It must be at least the prospective fault at the point of connection, and up to 3 s it converts between durations with I squared t constant (Clause 9.3.2).
- **Assumed loading factor** — The fraction of their rated current the outgoing circuits of an assembly are assumed to draw together when the manufacturer and the user have not agreed actual currents: AS/NZS 61439.2 Table 101 gives 0.9 for two or three circuits, 0.8 for four or five, 0.7 for six to nine and 0.6 for ten or more; AS/NZS 61439.3 Table 101 is one step lower for a distribution board for ordinary persons. The rated diversity factor times the circuit ratings must cover it (Clause 5.4).
- **Rated impulse withstand voltage (Uimp)** — The 1.2/50 microsecond impulse an assembly's insulation withstands, chosen from AS/NZS 61439.1 Table G.1 by the system voltage and the overvoltage category of the installation point: 6 kV at the origin of a 230/400 V installation (category IV), 4 kV at distribution circuit level (III). Table 1 turns it into the minimum clearance in air.
- **Bay (section)** — One vertical cubicle of a floor-standing switchboard, bolted alongside its neighbours to form the assembly. The calculator packs the functional sections into bays of standard width and reports the bay count alongside the overall width, because switchrooms and transport access are planned bay by bay.
- **Distribution chassis** — The DIN-rail assembly inside a section that carries the small outgoing final subcircuits. Circuits are converted into chassis "ways" on an 18 mm planning pitch, banded into a standard chassis width; ways beyond one rail row add height rather than width.
- **Way** — One pole position on a distribution chassis. A 1P device occupies one way, a 2P or 1P+N device two, and a 3P+N or 4P device four, so the way count (not the circuit count) is what drives chassis width.
- **Incomer** — The incoming main switch or main protective device at the origin of the switchboard, sized from the switchboard rating. Whether it is a switch-fuse unit, a moulded-case circuit breaker (MCCB) or an air circuit breaker (ACB) sets its compartment depth, which in turn can govern the depth of the whole board.
- **MEN link** — The multiple earthed neutral link that bonds the neutral bar to the earth bar at the main switchboard, required by AS/NZS 3000:2018 for a MEN system. It needs an accessible zone in the board, so the calculator allows for it as its own functional section with a height that scales with the main rating.
- **CT metering chamber** — A dedicated compartment housing current transformers and metering for supplies too large to meter directly. Its width allowance depends on the metering purpose (EMS/BMS monitoring, private metering, tenant sub-metering or revenue-grade metering), and above a threshold number of metered feeders it becomes a shared board-level section rather than CTs inside each feeder.
- **Design verification** — The AS/NZS 61439.1 process by which a manufacturer demonstrates that an assembly design complies: by testing, by calculation or comparison with a tested reference design, or by satisfying design rules. Enclosure dimensions are an outcome of design verification, not an input that can be computed independently of the tested system.
- **Verified assembly** — A switchboard built within a manufacturer's design-verified system, so its busbar bracing, temperature rise, short-circuit withstand, clearances and enclosure dimensions are all covered by that verification. The final dimensions of a real board come from the verified assembly; a functional-section estimate like this one is a planning figure that precedes it.
- **Spare capacity** — The allowance, usually expressed as a percentage and commonly 20-25%, for circuits added after handover. In this calculator it expands the chassis design ways and reserves additional feeder space, and discrete spare bays can be added on top for whole future sections.
- **IP rating** — The AS 60529 ingress protection classification of the enclosure (for example IP40 indoors, IP56 or IP66 outdoors). A higher IP rating requires deeper gland and sealing zones, so it sets a depth floor that the calculator applies when it exceeds the depth implied by the rating band and the switchgear compartment.

## Frequently asked questions

### Does AS/NZS 61439 tell me how big a switchboard should be?

No. AS/NZS 61439 is a performance and verification standard, not a dimensional catalogue: it has no universal formula that turns a load schedule into an enclosure size. The Elecas calculator builds a preliminary footprint from your functional sections (incomer, metering, chassis, feeders, spare) for early space planning; the final dimensions must come from the switchboard manufacturer's verified assembly system.

### What Form of separation should I specify for a main switchboard?

Form 3b or Form 4b is common for main switchboards where one circuit must be workable without isolating the whole board; Form 1 or Form 2a/2b suits smaller distribution boards. Higher Forms add internal barriers and terminal segregation, so the same electrical content does need more space in practice: but the amount is specific to the manufacturer's tested cubicle system, so the Elecas calculator records your selected Form against the estimate as a verified-assembly constraint rather than applying an invented universal width or depth adder. Confirm the dimensional effect with the switchboard builder for the range you intend to use.

### How much spare capacity should a switchboard have?

A common convention is 20-25% spare, applied to both the chassis ways and the feeder space. The right figure depends on the client brief and how likely the installation is to grow. The calculator takes the percentage as an input and includes it in the reported width, so the footprint you reserve already carries the growth allowance.

### What peak current must the switchboard busbars withstand?

The rated peak withstand current Ipk has to be at least the peak of the prospective fault, and AS/NZS 61439.1 Table 7 gives the factor between the r.m.s. fault and its peak: n is 1.5 up to 5 kA, 1.7 up to 10 kA, 2.0 up to 20 kA, 2.1 up to 50 kA and 2.2 above. A 25 kA fault therefore needs a 52.5 kA peak rating. The calculator shows both figures beside the Icw band, and restates the band for 0.2 s and 3 s using the I squared t constant rule of Clause 9.3.2.

### Is my switchboard a distribution board to AS/NZS 61439.3 or an assembly to 61439.2?

It is a 61439.3 distribution board (DBO) only if ordinary persons operate it and it sits inside the Part 3 scope: rated up to 250 A, outgoing circuits up to 125 A, no more than 300 V to earth. A main switchboard in a switchroom, or any board above those limits, is a power switchgear and controlgear assembly to 61439.2. The parts differ in their assumed loading table, their neutral rule and the minimum overvoltage category, so the calculator asks who operates the board and reports the part.

### How big should the main busbar be?

The calculator suggests the least bare copper in AS/NZS 61439.1 Annex N Table N.1 whose operating current covers the main rating at 55 degrees enclosure air and 70 degrees conductor, one bar per phase before two, and reports the watts per metre it dissipates. It is a guide: a bar verified by test in the manufacturer's system may be smaller, and a hotter enclosure needs more copper by the Table N.2 factor.

### Can I use the result for tender pricing and switchroom planning?

Yes, that is exactly what it is for: reserving floor area in a switchroom, sizing a riser and setting a tender allowance at concept stage. Treat the output as a preliminary functional-section estimate, then confirm the final busbar, terminal, thermal, clearance and enclosure dimensions with the switchboard builder's verified assembly before construction.

## Related Elecas pages

- [Switchroom Sizing Calculator (the room around the board)](https://elecas.com.au/calculator/switchroom-sizing)
- [Maximum Demand Calculator](https://elecas.com.au/calculator/max-demand)
- [Cable Size Calculator](https://elecas.com.au/calculator/cable-selection)
- [Arc Flash Calculator](https://elecas.com.au/calculator/arc-flash)
- [Selectivity Calculator (Breaker Discrimination)](https://elecas.com.au/calculator/selectivity)
- [Lightning Risk Assessment Calculator](https://elecas.com.au/calculator/lightning-risk)
- [Generator Sizing Calculator](https://elecas.com.au/calculator/generator-sizing)
- [EleCAD Single Line Diagram Builder](https://elecas.com.au/elecad)
- [Voltage Drop Calculator](https://elecas.com.au/calculator/voltage-drop)
- [Design Guides](https://elecas.com.au/design-guide)
- [Table C2 Non-Domestic Maximum Demand](https://elecas.com.au/calculator/c2)
- [Table C3 Energy Demand (VA/m²)](https://elecas.com.au/calculator/c3)
- [Emergency Lighting Design Guide](https://elecas.com.au/design-guide/emergency-lighting)
- [Calculation Verification](https://elecas.com.au/verification)

## About this page

Written and reviewed by Wisam Tozah, Associate Electrical Engineer (B.Eng (Electrical), MIEAust, CPEng, NER, NSW DBP, NSW PRE, APEC, IntPE(Aus)), Sydney, Australia. How the calculations are tested and reviewed: https://elecas.com.au/verification. Profile: https://elecas.com.au/creator.

Usage: this page may be read, indexed, retrieved and cited, including as grounding for an AI answer, with attribution to Elecas and a link to https://elecas.com.au/calculator/switchboard-sizing. Reproducing it, training a model on it, or using it to build a derivative or competing site is not licensed. Terms: https://elecas.com.au/terms. Machine-readable policy: https://elecas.com.au/ai-usage-policy.json

Site index for assistants: https://elecas.com.au/llms.txt — full content: https://elecas.com.au/llms-full.txt
