ElecAS
Cable Size Calculator — AS/NZS 3008.1.1:2025 Cable Sizing for Australia
Free, browser-based AS/NZS 3008.1.1:2025 cable size calculator built for Australian electrical engineers, designers, electricians, estimators and contractors. Enter your design current, supply phase, conductor material, insulation, construction, installation method, route length and protection device — the calculator returns the smallest compliant cable size after running every check that AS/NZS 3000 and AS/NZS 3008.1.1 require: current-carrying capacity with k1 ambient, k2 grouping, k3 soil thermal resistivity and k4 depth-of-burial derating; protection coordination Ib ≤ In ≤ Iz; voltage drop against your per-segment limit and the AS/NZS 3000 Clause 3.6.2 envelope (5%, with the customary 7% design allocation where supply is from an on-site substation); device breaking capacity against the prospective fault current; the I²t ≤ k²S² adiabatic short-circuit withstand check on both the active and the earth conductor using AS/NZS 3008.1.1:2025 Table 5.1 k-values (111.2 Cu/PVC, 142.9 Cu/XLPE, 73.7 Al/PVC, 94.6 Al/XLPE), with the earth conductor checked at both ends of the run; and earth-fault loop impedance computed from the full R + jX cable loop per the AS/NZS 3000 Appendix B4 framework, with the trip current Ia pulled directly from the linked Schneider Electric circuit protection database (Im for thermal-magnetic MCBs and MCCBs, Ii for electronic-trip MCCBs and ACBs). Three conductor types — Copper (Cu), Copper Flexible, Aluminium (Al) — and five insulation classes — V-75 PVC, X-90 XLPE, R-90 elastomeric, X-110 XLPE and R-110 elastomeric (the calculator's essential-safety / fire-rated option per AS/NZS 3013) — are supported, along with the full AS/NZS 3008.1.1 Table 3 installation method library M1 to M11. Auto insulation resolves V-75 up to 16 mm² and X-90 above for a chosen size (auto-sizing assumes X-90), construction Auto resolves multi-core up to 95 mm² and single-core from 120 mm² upward, and R-110 is selected manually for fire-rated and essential-services sections. Built-in support for parallel runs, separate earth-conductor sizing per Table 5.1, full project metadata capture and a branded PDF cable selection report you can drop straight into a design submission.
Why this page matters
Free, browser-based AS/NZS 3008.1.1:2025 cable size calculator built for Australian electrical engineers, designers, electricians, estimators and contractors. Enter your design current, supply phase, conductor material, insulation, construction, installation method, route length and protection device — the calculator returns the smallest compliant cable size after running every check that AS/NZS 3000 and AS/NZS 3008.1.1 require: current-carrying capacity with k1 ambient, k2 grouping, k3 soil thermal resistivity and k4 depth-of-burial derating; protection coordination Ib ≤ In ≤ Iz; voltage drop against your per-segment limit and the AS/NZS 3000 Clause 3.6.2 envelope (5%, with the customary 7% design allocation where supply is from an on-site substation); device breaking capacity against the prospective fault current; the I²t ≤ k²S² adiabatic short-circuit withstand check on both the active and the earth conductor using AS/NZS 3008.1.1:2025 Table 5.1 k-values (111.2 Cu/PVC, 142.9 Cu/XLPE, 73.7 Al/PVC, 94.6 Al/XLPE), with the earth conductor checked at both ends of the run; and earth-fault loop impedance computed from the full R + jX cable loop per the AS/NZS 3000 Appendix B4 framework, with the trip current Ia pulled directly from the linked Schneider Electric circuit protection database (Im for thermal-magnetic MCBs and MCCBs, Ii for electronic-trip MCCBs and ACBs). Three conductor types — Copper (Cu), Copper Flexible, Aluminium (Al) — and five insulation classes — V-75 PVC, X-90 XLPE, R-90 elastomeric, X-110 XLPE and R-110 elastomeric (the calculator's essential-safety / fire-rated option per AS/NZS 3013) — are supported, along with the full AS/NZS 3008.1.1 Table 3 installation method library M1 to M11. Auto insulation resolves V-75 up to 16 mm² and X-90 above for a chosen size (auto-sizing assumes X-90), construction Auto resolves multi-core up to 95 mm² and single-core from 120 mm² upward, and R-110 is selected manually for fire-rated and essential-services sections. Built-in support for parallel runs, separate earth-conductor sizing per Table 5.1, full project metadata capture and a branded PDF cable selection report you can drop straight into a design submission. This static content is published so the canonical route has meaningful crawlable HTML even before the interactive application hydrates.
Who this page is for
Electrical engineers, designers, electricians, estimators and contractors sizing copper, copper flexible or aluminium conductors for consumer mains, submains, final subcircuits, motor circuits and essential / fire-rated services under AS/NZS 3000:2018, AS/NZS 3008.1.1:2025, AS/NZS 3013 and the National Construction Code (NCC).
Relevant standards
- AS/NZS 3008.1.1:2025 (Cable Selection — Tables 3.9–3.20 capacity, 3.33–3.48 derating, 4.1–4.10 impedance, 5.1 k-values)
- AS/NZS 3000:2018 (Wiring Rules, including Clauses 2.5.3, 3.4, 3.6, 5.7.2 and Appendix B4)
- AS/NZS 3000 Table 5.1 (Earthing Conductor Sizing)
- AS/NZS 3000 Table 8.1 (Maximum Earth-Fault Loop Impedance)
- AS/NZS 3013 (Fire-Rated Wiring Systems — WS Classification)
- AS 60038 (Standard Voltages — 230 V +10% / -6%)
- National Construction Code (NCC) — essential services
What this tool helps with
- Runs every AS/NZS 3000 and AS/NZS 3008.1.1:2025 cable selection check in one pass — current carrying capacity (with full k1·k2·k3·k4 derating), Ib ≤ In ≤ Iz protection coordination, voltage drop, breaking capacity, I²t ≤ k²S² thermal withstand on the active and the earth conductor, and earth-fault loop impedance.
- Applies the four AS/NZS 3008.1.1 correction factors automatically from Tables 3.33–3.48 — ambient air or soil temperature (k1), grouping (k2), soil thermal resistivity (k3) and depth of burial (k4) — and shows the resulting Total Derating Factor in the configuration panel.
- Three conductor options — Copper (Cu), Copper (Flexible) and Aluminium (Al) — with calculator-aware impedance values for fine-stranded flexible cores and the aluminium-specific insulation restrictions.
- Five insulation classes — V-75 PVC, X-90 XLPE, R-90 elastomeric, X-110 XLPE, and R-110 elastomeric (the essential-safety / fire-rated option for fire pumps, mechanical essential boards, fire-mode lifts and fire detection / EWIS per AS/NZS 3013).
- Auto insulation picks V-75 PVC up to 16 mm² and X-90 XLPE above for a chosen size (auto-sizing assumes X-90), and construction Auto picks multi-core up to 95 mm² and single-core from 120 mm² upward — the same conventions used on Australian commercial and industrial installations. R-110 elastomeric is selected manually for fire-rated sections.
- Ten construction layouts covering single-phase and three-phase: 2C+E, 2C, 2x1C+E, 2x1C, 4C+E, 3C+E, 4C, 4x1C+E, 3x1C+E and 4x1C — with the calculator counting loaded conductors when it pulls the AS/NZS 3008.1.1 capacity table.
- Full AS/NZS 3008.1.1 Table 3 installation method library — unenclosed in air (M1–M4), enclosed in conduit (M5–M8), buried direct (M9) and in underground enclosures (M10–M11) — with single-core arrangement options (trefoil, flat-touching, flat-spaced) feeding the impedance lookup.
- Voltage drop calculated by the impedance method Z = √(R² + X²) per AS/NZS 3008.1.1, with a one-toggle switch to the actual-PF projection Vc = R·cosφ + X·sinφ for tighter sizing on known-PF loads, and the per-segment limit checked against your design split (typically 1% mains, 1.5–2% submains, 2–2.5% final subcircuits inside the 5% Cl. 3.6.2 envelope, or the customary 7% substation allocation).
- Earth-fault loop impedance computed from the full cable impedance loop Zs = Ze + √((R_loop·L)² + (X_loop·L)²) per the AS/NZS 3000 Appendix B4 framework, with the trip current Ia pulled from the linked Schneider Electric circuit protection database (Im for MCB / thermal-magnetic MCCB, Ii for electronic-trip MCCB / ACB) and a fuse fallback when no breaker record applies.
- Native parallel-runs support per AS/NZS 3000 Cl. 3.4.3 with a separate earth conductor stepper, automatic AS/NZS 3000 Table 5.1 earth sizing, and a project metadata block (project name, number, address, designer, revision) that flows into the exported PDF cable selection report.
- Built and reviewed by a Chartered Professional Engineer (CPEng, NER, NSW DBP, NSW PRE, APEC, IntPE Aus) — see the Verification page for the testing and review process.
How to size a cable under AS/NZS 3008.1.1 and AS/NZS 3000
- Enter design current (Ib) — Enter the maximum continuous design current the circuit will carry. For motors use the nameplate full-load current; for distribution circuits use the maximum demand from AS/NZS 3000 Section 2.
- Select phases and protection device — Set Phases to 1 or 3 and pick the upstream protective device (MCB curve B/C/D, MCCB, ACB or fuse). The device rating In must satisfy Ib ≤ In ≤ Iz per AS/NZS 3000 Cl. 2.5.3.1.
- Choose conductor, insulation and construction — Pick Copper (Cu), Copper Flexible or Aluminium; pick V-75, X-90, R-90, X-110 or R-110 insulation (or leave Auto); pick a multi-core or single-core construction with the appropriate number of cores for the loading.
- Choose AS/NZS 3008.1.1 installation method — Select Method M1–M4 (unenclosed in air), M5–M8 (enclosed in conduit), M9 (buried direct) or M10–M11 (in underground enclosure) to match the physical install.
- Apply derating factors — Switch on Apply Derating and enter ambient temperature, number of grouped circuits, soil thermal resistivity and depth of burial. The calculator pulls k1·k2·k3·k4 from AS/NZS 3008.1.1 Tables 3.33–3.48 automatically.
- Set route length and voltage drop budget — Enter the cable route length in metres and the per-segment voltage drop allowance — typically 1% for consumer mains, 1.5–2% for submains and 2–2.5% for final subcircuits, inside the AS/NZS 3000 Cl. 3.6.2 5% envelope (or the customary 7% substation allocation).
- Enter fault current and clearing time — Provide the prospective short-circuit current Isc at the cable origin and the upstream device clearing time so the calculator can run the adiabatic I²t ≤ k²S² check on the active and the earth conductor.
- Set external impedance Ze for Zs check — Enter the supply external impedance Ze (default 0.35 Ω for residential or 0.02 Ω for an on-site substation). The calculator computes Zs = Ze + √((R_loop·L)² + (X_loop·L)²) from the full cable impedance and verifies Zs ≤ U₀/Ia against the AS/NZS 3000 Cl. 5.7.2 disconnection time.
- Review pass/fail pills and export the PDF report — Each compliance check shows a pass/fail pill. When every check passes, fill in the project metadata block and export the branded PDF cable selection report for submission.
Cable sizing under AS/NZS 3008.1.1:2025 — practical guide
Standards and methodology
The ElecAS cable size calculator reads tabulated values directly from the current Australian/New Zealand standards — no rules of thumb and no interpolation beyond the published data. AS/NZS 3008.1.1:2025 is the dominant reference: current-carrying capacity comes from the Section 3 tables (Tables 3.9 to 3.20 for the supported constructions) selected by the chosen installation method, conductor and insulation; voltage drop uses the impedance values published in Tables 4.1 to 4.10 (R and X per kilometre at the conductor operating temperature); derating factors come from Tables 3.33 to 3.48; and short-circuit k-values for the adiabatic check come from Table 5.1.
AS/NZS 3000:2018 (the Wiring Rules) drives the compliance checks. Clause 2.5.3.1 sets protection coordination Ib ≤ In ≤ Iz. Clause 3.4.1 and Table 3.3 fix minimum conductor sizes. Clause 3.4.3 governs parallel runs. Clause 3.6.2 sets the 5% voltage drop limit from the point of supply (a 7% allocation is a common design convention where supply is from an on-site substation). Appendix B4 frames the earth-fault loop impedance requirement — the tool computes the full R + jX loop rather than the resistance-only shortcut. Clause 5.7.2 sets disconnection times (0.4 s for socket-outlet final subcircuits up to 63 A, hand-held Class I and portable equipment; 5 s for other circuits). Table 5.1 fixes the minimum earthing conductor and Table 8.1 publishes the corresponding maximum Zs values. AS 60038 sets the nominal voltage envelope (230 V +10% / −6%) that the 5% drop limit feeds into.
The six compliance checks
Cable selection requires more than one check. The calculator verifies current-carrying capacity with correction factors, voltage drop, short-circuit thermal withstand and earth-fault loop impedance/disconnection time. It also verifies protection coordination per AS/NZS 3000 Cl. 2.5.3.1 (Ib ≤ In ≤ Iz) and short-circuit breaking capacity at the device. Each check is reported with its own pass/fail pill in the result summary.
Capacity is the cable’s tabulated rating after the four derating factors are applied (ambient temperature k1, grouping k2, soil thermal resistivity k3 and depth of burial k4). The thermal withstand uses the adiabatic equation I²t ≤ k²S² on both the active and the earth conductor with the Table 5.1 k-value matched to the resolved insulation, and the earth conductor is checked for a fault at both ends of the run. The earth-fault loop impedance check computes the full impedance loop Zs = Ze + √((R_loop·L)² + (X_loop·L)²) and verifies Zs ≤ U₀ / Ia for the disconnection time required by Cl. 5.7.2.
Voltage drop split across the path
AS/NZS 3000:2018 Cl. 3.6.2 limits the total drop from the point of supply to any load to 5% of nominal when the supply comes from the network — 11.5 V on a 230 V single-phase circuit and 20 V line-to-line on a 400 V three-phase circuit. Where the point of supply is at a consumer-owned on-site substation, designers commonly allocate up to 7% — a design convention rather than a figure published in Cl. 3.6.2.
The total is a budget for the whole path. A conservative allocation that gives sensible headroom at the final outlet is roughly 1.0% on consumer mains, 1.5% to 2.0% on submains, and 2.0% to 2.5% on final subcircuits. The calculator’s Maximum Voltage Drop field is the per-segment limit you want this cable checked against.
Conductor, insulation and construction choices
Copper is the default in Australia. Aluminium is offered for large mains and submains (typically 70 mm² and above) where weight and cost favour it, but it has only ~60% of copper’s conductivity, cold-flows under terminal pressure, oxidises and reacts galvanically with copper. The calculator restricts the insulation menu to V-75, X-90 and R-90 when aluminium is selected because the 110 °C products are only manufactured in copper.
V-75 PVC is the calculator’s default for lighting, general power and small submains; the Auto rule selects V-75 for any size up to 16 mm². X-90 XLPE carries roughly 25–30% more current in the same cross-section with a higher Table 5.1 k-value (142.9 vs 111.2); Auto selects X-90 once the resolved cable is larger than 16 mm². The deciding factor in practice is termination temperature — most MCBs, switch-disconnectors and lug terminals are rated for 75 °C terminations, so even an X-90 cable has to be sized off the 75 °C column at those devices.
R-110 elastomeric is the calculator’s fire-rated option (R-HF-110 / R-E-110 halogen-free elastomeric circuit-integrity cables) — pick it manually from the Insulation selector for essential-services sections. Construction Auto resolves to multi-core up to 95 mm² and single-core from 120 mm² upwards, with the earth integral by default.
Derating and installation methods
Switch the Apply Derating toggle on and the four AS/NZS 3008.1.1 correction factors fold in automatically: k1 for ambient air or soil temperature (Tables 3.44 and 3.45), k2 for grouping of circuits (Tables 3.33 to 3.43), k3 for soil thermal resistivity on buried cables (Table 3.48), and k4 for depth of burial (Tables 3.46 and 3.47). Their product is the Total Derating Factor shown in the configuration panel — typically between 0.5 and 1.0 in real installations.
AS/NZS 3008.1.1 publishes the entire buried current carrying capacity table at a reference resistivity of 1.2 K·m/W. Most moist Australian soils sit around 1.5 K·m/W, dry sandy soils run 2.0 to 2.5 K·m/W, and crushed-rock or thermally enhanced sand can go below 1.0 K·m/W. Use the geotechnical report value or 1.5 K·m/W as a conservative default.
The Installation Method selector matches the AS/NZS 3008.1.1 method codes to the physical install. Unenclosed in air (M1–M4) covers tray, ladder or clipped direct; Enclosed in conduit (M5–M8) covers surface or in-wall conduit; Buried direct (M9) covers cables in a trench; and In underground enclosure (M10–M11) covers cables in buried conduits or ducts. Buried installations do not automatically mean smaller cables.
Short-circuit thermal withstand and earth-fault loop impedance
Short-circuit withstand tends to govern when prospective fault currents are high and the upstream protection has a relatively slow clearing time. Typical clearing-time presets are about 10 ms for an HRC fuse, 20 ms for a current-limiting MCB, 40 ms for a standard MCCB, 80 ms for an electronic-trip MCCB and 100 ms for an ACB. The adiabatic equation I²t ≤ k²S² is applied to both the active and the earth conductor with k from AS/NZS 3008.1.1:2025 Table 5.1: 111.2 for copper PVC (≤300 mm²; 98.5 above), 142.9 for copper 90 °C XLPE/elastomer, 131.8 for the copper 110 °C classes, 73.7 for aluminium PVC and 94.6 for aluminium XLPE. The earth conductor is checked for a fault at both ends of the run.
For earth-fault loop impedance the calculator implements the AS/NZS 3000 Appendix B4 framework with the full cable impedance: Zint = √((R_loop·L)² + (X_loop·L)²) / 1000, Zs = Ze + Zint, and the pass condition is Zs ≤ U₀ / Ia with U₀ = 230 V. The trip current Ia is read from the linked Schneider Electric circuit protection database — Im for MCBs and thermal-magnetic MCCBs, Ii for electronic-trip MCCBs and ACBs, with a generic fuse fallback when no breaker record applies.
Earth conductor sizing and parallel runs
The minimum copper protective earthing conductor comes from AS/NZS 3000 Table 5.1. The calculator’s Earth Conductor selector defaults to Auto and follows the table: 1, 1.5 and 2.5 mm² actives keep an earth equal to the active; from 4 to 10 mm² the earth steps down (4 and 6 mm² actives resolve to 2.5 mm² earth, a 10 mm² active to 4 mm²); from 16 mm² upwards the earth is roughly half the active CSA (50 → 16 mm², 95 → 25 mm², 150 → 50 mm², 240 → 95 mm²). Table 5.1 caps the copper earth at 120 mm² for 400–630 mm² actives (25% of the active above 630 mm²); the calculator keeps the half-size convention there, which exceeds that minimum. With aluminium actives Table 5.1 permits a smaller copper earth at the same active size. Table 5.1 is only the minimum — the earth still has to pass the adiabatic check I²t ≤ k²S² at both ends of the run and the Zs loop check, which the calculator runs automatically, upsizing the earth (never beyond the active size) if needed.
For parallel runs, set the Parallel Runs stepper to the number of identical sets and the design current per run becomes Ib / n. AS/NZS 3000 Cl. 3.4.3 requires every run to be no smaller than 4 mm² and identical in length, cross-sectional area, conductor material and installation method. Parallel single-core runs are usually grouped and may also need the AS/NZS 3008.1.1 Tables 3.33–3.43 grouping factor.
Fire-rated and essential-services cables
A fire-rated cable keeps circuit integrity for a specified period under fire exposure so the load it feeds keeps operating from the mains during evacuation. AS/NZS 3013 publishes the wiring system (WS) classification — e.g. WS52W combines a 1100 °C fire test with water spray and mechanical impact.
Fire rating is required where the load has no autonomous backup and must keep drawing mains power during the fire — fire pumps and sprinkler controls (AS 2941, AS 4214), mechanical services essential boards, emergency / fire-mode lifts, fire detection and EWIS / sound systems where the head-end has no on-board battery (AS 1670, AS 7240), and any other circuits the NCC designates as essential (Specification E1.5 / E2.2). Emergency and exit luminaires (AS/NZS 2293) and the FIP have integral batteries and do not require fire-rated cables.
The support system has to hold the cable in place for the full WS-rated duration. AS/NZS 3013 calls for stainless-steel ties or metallic clips, reduced fixing spacings of about 350 mm or less, tested fire-rated cleats matched to the cable family, and heavy-gauge steel trays with documented fire test results. Penetrations through fire-rated walls or floors must use a tested seal.
Frequently asked questions
What standards does the ElecAS cable size calculator use?
- AS/NZS 3008.1.1:2025 supplies the current carrying capacity tables (Section 3 — Tables 3.9 to 3.20 for the supported constructions), derating factors (Tables 3.33 to 3.48), conductor R and X values for voltage drop (Tables 4.1 to 4.10) and short-circuit k-values (Table 5.1). AS/NZS 3000:2018 drives compliance — Cl. 2.5.3.1 protection coordination, Cl. 3.4 minimum sizes, Cl. 3.6.2 voltage drop limit (5% from the point of supply; a 7% allocation is a common design convention where supply is from an on-site substation), Cl. 5.7.2 disconnection times, the Appendix B4 earth-fault loop framework, Table 5.1 earth conductor sizing and Table 8.1 maximum Zs. AS/NZS 3013 covers fire-rated wiring systems and AS 60038 sets the 230 V +10% / -6% voltage envelope.
What checks does the cable size calculator run?
- Six checks on every result: (1) current carrying capacity after k1·k2·k3·k4 derating; (2) protection coordination Ib ≤ In ≤ Iz per AS/NZS 3000 Cl. 2.5.3.1; (3) voltage drop against your per-segment limit and the Cl. 3.6.2 envelope; (4) device breaking capacity against the prospective fault current; (5) the adiabatic I²t ≤ k²S² short-circuit thermal withstand check on both the active and the earth conductor using AS/NZS 3008.1.1:2025 Table 5.1 k-values, with the earth checked at both ends of the run; and (6) earth-fault loop impedance computed from the full R + jX cable loop, Zs = Ze + √((R·L)² + (X·L)²), against the Cl. 5.7.2 disconnection time.
How much voltage drop is allowed under AS/NZS 3000, and how do I split it across consumer mains, submain and final subcircuit?
- AS/NZS 3000:2018 Cl. 3.6.2 limits the total drop from the point of supply to any load to 5% of nominal when the supply comes from the network — 11.5 V on a 230 V single-phase circuit and 20 V line-to-line on a 400 V three-phase circuit. Where the point of supply is at a consumer-owned on-site substation, designers commonly allocate up to 7% — a design convention rather than a figure published in Cl. 3.6.2. The total is a budget for the whole path, not a per-segment limit. A conservative allocation is roughly 1.0% on consumer mains, 1.5% to 2.0% on submains, and 2.0% to 2.5% on final subcircuits. The calculator’s Maximum Voltage Drop field is the per-segment limit checked against this cable.
What voltage drop limit applies to consumer mains in Australia?
- AS/NZS 3000 Cl. 3.6.2 does not publish a separate limit for consumer mains — the 5% total (or the customary 7% allocation from an on-site substation) applies from the point of supply to the load. Designers conventionally hold the mains segment to roughly 1.0% so the submain and final subcircuit downstream still have room to comply. The calculator checks whatever per-segment allowance you enter and the result still has to satisfy the appliance operating-voltage range once it is combined with the rest of the path.
Does cable temperature affect voltage drop?
- Yes — copper resistance rises about 0.4% per °C, and AS/NZS 3008.1.1 publishes its impedance tables (Tables 4.1 to 4.10) at the maximum continuous operating temperature of each insulation class. The calculator picks the correct row automatically once you select the insulation: 75 °C values for V-75 PVC, 90 °C values for X-90 XLPE and R-90 elastomer, and 110 °C values for X-110 XLPE and R-110 elastomer. Voltage drop on a fully loaded XLPE cable is therefore a few percent worse than the same conductor sized in PVC because the conductor is hotter at design current.
Should I use worst-case PF or the actual power factor for voltage drop?
- AS/NZS 3008.1.1 publishes two methods and the calculator offers both via the Worst Case PF toggle. With it on (the default) the cable component is the full impedance Zc = √(R² + X²) — conservative and bounded regardless of the load plant that ends up connected, suitable for distribution boards, mains and mixed loads. With the toggle off the calculator uses the actual-PF projection Vc = R·cosφ + X·sinφ from the entered power factor; real loads at lagging PF give a smaller drop than the worst-case envelope, allowing tighter sizing where the load PF is known and stable (a single dedicated motor, VFD or large fixed plant).
How is voltage drop calculated for single-phase vs three-phase cables?
- The base formula is the same: Vd = (L × Ib × Vc) / 1000, with L in metres, Ib in amps and Vc the cable’s mV/A·m factor. What changes is the multiplier baked into Vc to account for the loop. On single-phase circuits the current returns through the neutral, so Vc = 2·Z. On three-phase line-to-line drop the geometry gives Vc = √3·Z. The calculator picks the correct factor automatically from the Phases selector at the top of the configuration panel.
What size cable do I need for a 32A circuit in Australia?
- For a single-phase 32 A circuit in copper V-75, the AS/NZS 3008.1.1:2025 tables give 4 mm² unenclosed (34–37 A spaced or touching) but 6 mm² enclosed in conduit (Method M5 — 4 mm² tabulates 30 A enclosed, just short of 32 A). A three-phase 32 A circuit derates further because three conductors are loaded, and longer runs or tighter voltage-drop allowances often push the result up a size. Re-run the calculator for your actual phasing, length, ambient temperature and grouping, then verify short-circuit withstand and Zs against the upstream device.
What size cable do I need for a 63A circuit?
- Reference: copper, three single-cores in conduit on a wall (Method M5), per the AS/NZS 3008.1.1:2025 tables. V-75 PVC copper lands at 25 mm² for capacity (16 mm² tabulates 62 A, just short of 63 A); X-90 XLPE copper drops to 16 mm² (10 mm² tabulates 56 A), subject to terminal temperature ratings. Buried installations do not automatically mean smaller cables: direct-buried (M9) only outperforms M5 at the AS/NZS 3008.1.1 reference soil resistivity of 1.2 K·m/W and shallow burial. Most Australian soils sit at 1.5–2.5 K·m/W which derates buried capacity significantly, and buried-in-enclosure (M10) ratings are often similar to or lower than M5. Re-run the calculator with your actual soil resistivity, depth and grouping.
What size cable do I need for a 100A submain?
- A 100 A copper submain typically falls around 25–35 mm² depending on installation method, insulation type, conductor arrangement and derating. Three single-core copper V-75 cables in conduit on a wall (Method M5) land at 35 mm², which tabulates exactly 100 A at reference conditions (no headroom for derating). Aluminium will generally require a larger size (around 70 mm² in the same scenario since 50 mm² aluminium tabulates 92 A in M5). Voltage drop becomes the governing constraint on long runs or where the upstream allowance is tight.
What size cable for a 200A consumer mains?
- Reference: three single-cores in conduit on a wall (Method M5), per the AS/NZS 3008.1.1:2025 tables. Copper V-75 PVC lands at 120 mm² for capacity (95 mm² tabulates 183 A); copper X-90 XLPE drops to 95 mm² at 220 A (70 mm² tabulates 183 A), subject to terminal temperature ratings; aluminium V-75 PVC steps up to 185 mm² (150 mm² tabulates 190 A and 120 mm² only 169 A in M5). Voltage drop on long mains often governs — keep this segment to about 1% allowance to leave room for the submain and final subcircuit.
How do I derate a cable for grouping and ambient temperature?
- Switch the Apply Derating toggle on and the calculator pulls all four AS/NZS 3008.1.1 correction factors at once: k1 for ambient air or soil temperature (Tables 3.44 and 3.45), k2 for grouping of circuits (Tables 3.33 to 3.43), k3 for soil thermal resistivity on buried cables (Table 3.48) and k4 for depth of burial (Tables 3.46 and 3.47). Their product is the Total Derating Factor shown in the configuration panel — typically between 0.5 and 1.0 in real installations. The calculator sizes the cable so Iz_actual = Iz_table × k1 × k2 × k3 × k4 stays at or above the design current Ib.
When does grouping derating apply?
- Grouping derating from AS/NZS 3008.1.1 Tables 3.33 to 3.43 applies whenever multiple loaded cables run in close proximity — bunched in a conduit, on a tray, in an enclosed run or tied together — because each cable raises the temperature of its neighbours and reduces the heat the conductor can dissipate. Switch on the Grouping sub-toggle, set the Number of Circuits to the actual number of loaded circuits in the group, and pick the matching arrangement (bunched in air, single layer on a tray, multilayer, or buried) — the calculator pulls the correct factor and folds it into k2. Spacing of at least one cable diameter between adjacent cables avoids the derating entirely on most installation methods.
Why does soil thermal resistivity matter for buried cables?
- A buried cable dissipates the heat from its losses through the surrounding soil. The higher the soil’s thermal resistivity, the more poorly it conducts that heat away, and the hotter the cable runs at any given current. AS/NZS 3008.1.1 publishes the entire buried current carrying capacity table at a reference resistivity of 1.2 K·m/W; Table 3.48 gives the k3 correction for any value above or below that. Most moist Australian soils sit around 1.5 K·m/W, dry sandy soils run from 2.0 to 2.5 K·m/W, and crushed-rock backfill or thermally enhanced sand can go below 1.0 K·m/W. Use the geotechnical report value or 1.5 K·m/W as a conservative default.
Which AS/NZS 3008.1.1 installation method should I select?
- The Installation Method selector matches the AS/NZS 3008.1.1 method codes to the physical install. Pick Unenclosed in air (Methods M1 to M4) for cables on a tray, ladder or clipped direct to a wall, with sub-options for spaced or touching arrangements; Enclosed in conduit (Methods M5 to M8) for surface or in-wall conduit and trunking; Buried direct (Method M9) for cables laid in a trench with controlled backfill; and In underground enclosure (Methods M10 to M11) for cables drawn into buried conduits or ducts. Buried installations do not automatically mean smaller cables — buried direct only outperforms an in-air install at reference resistivity and shallow burial.
Copper vs aluminium — which conductor should I size with?
- Copper is the default in Australia. It has higher conductivity for the same cross-section, better mechanical and fatigue strength, and terminates cleanly into standard lugs without specialist preparation. Aluminium is genuinely useful on large mains and submains (typically 70 mm² and above) where lower weight and cost outweigh the drawbacks, but it has only ~60% of copper’s conductivity (one or two sizes larger for the same current), cold-flows under terminal pressure demanding torque-controlled lugs and anti-oxidation paste, oxidises with a poorly-conducting oxide layer, and reacts galvanically with copper so any aluminium-to-copper joint needs a bimetallic lug. The calculator restricts the insulation menu to V-75, X-90 and R-90 when aluminium is selected because the 110 °C products are only manufactured in copper.
V-75 (PVC) vs X-90 (XLPE) — which insulation should I pick?
- V-75 PVC runs at 75 °C and is the cheapest construction; the calculator’s Auto rule selects V-75 for any size up to 16 mm². X-90 XLPE runs at 90 °C, carries roughly 25 to 30% more current in the same cross-section, and has a higher Table 5.1 k-value (142.9 vs 111.2 for copper) — Auto selects X-90 once the resolved cable is larger than 16 mm². The deciding factor in practice is termination temperature: most MCBs, switch-disconnectors and lug terminals are rated for 75 °C terminations, so even an X-90 cable has to be sized off the 75 °C column at those devices.
What is cable insulation and what does it do?
- The insulation is the dielectric layer surrounding each conductor. It prevents leakage between conductors and to earth at the operating voltage, sets the maximum continuous conductor temperature (which together with the installation method fixes the AS/NZS 3008.1.1 current carrying capacity), and sets the short-circuit k-value used in the Table 5.1 adiabatic check. The five Australian insulation classes are V-75 (PVC 75 °C), X-90 (XLPE 90 °C including X-90UV and X-HF-90 halogen-free variants), R-90 (Elastomeric 90 °C including R-EP-90, R-CPE-90 and R-HF-90), X-110 (XLPE 110 °C, X-HF-110 form), and R-110 (Elastomeric 110 °C, R-HF-110 and R-E-110 forms — the fire-rated option). The 110 °C options are only available with copper conductors.
How do I select the right cable insulation?
- Leave the Insulation selector on Auto and the calculator resolves V-75 PVC up to 16 mm² and X-90 XLPE above 16 mm² for a manually selected size (auto-sizing assumes X-90 since the size is not known yet) — the same convention most contractors and suppliers default to. For fire-rated and essential-services sections, pick R-110 elastomeric manually. Pick V-75 manually for general dry fixed wiring at 40 °C indoor ambients. Pick X-90 when capacity is tight, ambient is elevated, the run is heavily grouped, or you want the ~25 to 30% capacity uplift. Pick R-90 elastomeric for industrial, vibration-prone or harsh-environment runs. Pick X-110 when 90 °C XLPE is still capacity-limited. Pick R-110 for fire-rated and critical-service circuits. Always verify the terminal temperature rating of the upstream and downstream device.
How do I choose the number of cores for a cable?
- The Construction selector filters automatically once you set Phases. Single-phase offers four constructions: 2C+E (active, neutral, integral earth), 2C (active and neutral with a separate earth), 2x1C+E and 2x1C single-cores. Three-phase offers six: 4C+E (three actives, neutral, integral earth — for any submain or consumer main feeding single-phase loads), 3C+E (three actives plus earth — balanced three-phase loads such as motors), 4C (separate earth), and the corresponding single-core layouts (4x1C+E, 3x1C+E, 4x1C). Auto resolves to multi-core up to 95 mm² and single-core from 120 mm² upwards, with the earth integral by default.
Single-core vs multi-core cables — which should I pick?
- Multi-core cables carry every conductor inside one outer sheath, which is easier to install, identify and terminate, fits cleanly through conduits, and ensures the conductors take the same path. The calculator’s Auto rule picks multi-core for any cable up to 95 mm². Single-core cables run each conductor in its own jacket — Auto switches to this from 120 mm² upwards because multi-core becomes physically unwieldy at those sizes and parallel runs (which AS/NZS 3000 Cl. 3.4.3 only allows on identical single-cores) become more common. For single-cores the Cable Arrangement selector lets you pick trefoil, flat-touching or flat-spaced; the calculator pulls the correct R and X values from the matching AS/NZS 3008.1.1 impedance table.
What is a fire-rated cable, and when is it required?
- A fire-rated cable keeps circuit integrity for a specified period (typically 30, 60, 90 or 120 minutes) under fire exposure so the load it feeds keeps operating from the mains during evacuation. AS/NZS 3013 publishes the wiring system (WS) classification — e.g. WS52W combines a 1100 °C fire test with water spray and mechanical impact. Fire rating is required where the load has no autonomous backup and must keep drawing mains power during the fire — fire pumps and sprinkler controls (AS 2941, AS 4214), mechanical services essential boards, emergency / fire-mode lifts, fire detection and EWIS / sound systems where the head-end has no on-board battery (AS 1670, AS 7240), and any other circuits the NCC designates as essential (Spec E1.5 / E2.2). Emergency and exit luminaires (AS/NZS 2293) and the FIP have integral batteries and do not require fire-rated cables. The ElecAS calculator sizes fire-rated cables as 110 °C elastomeric (R-110).
Do I need a fire-rated cable tray or support system?
- Yes. When the circuit is fire-rated the support system has to hold the cable in place for the full WS-rated duration — standard galvanised tray or PVC saddles lose structural integrity in minutes and the cable will fall before its insulation fails. AS/NZS 3013 calls for stainless-steel ties or metallic clips (PVC ties are prohibited), reduced fixing spacings of about 350 mm or less, tested fire-rated cleats matched to the cable family, and heavy-gauge steel trays with documented fire test results. Penetrations through fire-rated walls or floors must use a tested seal (intumescent collar, mortar or pillow) so the wall’s FRL is preserved. The fire-resisting integrity is only as good as the weakest link — cable, support, fixing, penetration seal and termination must all carry the specified rating.
What is the WS classification on a cable, and what does it mean?
- WS stands for Wiring System under AS/NZS 3013, and the code summarises three combined tests applied to the entire system rather than the cable alone. The W component is the fire test (subscript X = no fire, Y = lower-temperature exposure, Z = full 1100 °C exposure), the S component is the water-spray test, and the trailing numeral is the mechanical impact rating. Common designations on Australian projects include WS51W and WS52W (1100 °C fire combined with water spray and mechanical impact, longer duration on WS52W) and WS3X (mechanical impact only, no fire). The project’s fire engineering report specifies the required WS rating per circuit, and the cable, support system, cleats and terminations all have to meet or exceed that rating.
When is short-circuit thermal withstand the limiting factor?
- Short-circuit withstand tends to govern when prospective fault currents are high (close to the supply transformer or downstream of a large on-site substation) and the upstream protection has a relatively slow clearing time. The calculator’s Source Fault Current field carries the prospective Isc at the location of the cable, and Fault Clearing Time is the duration the protection takes to interrupt that fault — typical presets are about 10 ms for an HRC fuse, 20 ms for a current-limiting MCB, 40 ms for a standard MCCB, 80 ms for an electronic-trip MCCB and 100 ms for an ACB. The check is the adiabatic equation I²t ≤ k²S² on both the active and the earth conductor (the earth is checked for a fault at both ends of the run), with k from AS/NZS 3008.1.1:2025 Table 5.1: 111.2 for copper PVC (≤300 mm²; 98.5 above), 142.9 for copper 90 °C XLPE/elastomer, 131.8 for the copper 110 °C classes, 73.7 for aluminium PVC and 94.6 for aluminium XLPE.
How does the calculator check earth-fault loop impedance under AS/NZS 3000?
- The calculator implements the AS/NZS 3000 Appendix B4 earth-fault loop framework using the full cable impedance: Zint = √((R_loop·L)² + (X_loop·L)²) / 1000, where R_loop and X_loop sum the active and earth conductor values per kilometre at operating temperature (on small cables this reduces to the familiar resistance-only method). The total loop impedance is Zs = Ze + Zint, with Ze the external impedance of the supply (presets from 0.02 Ω at an on-site substation MSB to 0.35 Ω at a residential final circuit). The pass condition is Zs ≤ U₀ / Ia with U₀ = 230 V and Ia from the linked Schneider Electric breaker database — Im for MCBs and thermal-magnetic MCCBs, Ii for electronic-trip MCCBs and ACBs, with a generic fuse fallback. The disconnection time required by Cl. 5.7.2 is 0.4 s for socket outlets up to 63 A and portable equipment, and 5 s for fixed and distribution circuits.
What size earth conductor do I need?
- The minimum copper protective earthing conductor comes from AS/NZS 3000 Table 5.1. The calculator’s Earth Conductor selector defaults to Auto and follows the table: 1, 1.5 and 2.5 mm² actives keep an earth equal to the active; from 4 to 10 mm² the earth steps down (4 and 6 mm² actives resolve to 2.5 mm² earth, a 10 mm² active to 4 mm²); from 16 mm² upwards the earth is roughly half the active CSA (50 → 16 mm², 95 → 25 mm², 150 → 50 mm², 240 → 95 mm²). Table 5.1 caps the copper earth at 120 mm² for 400–630 mm² actives (25% of the active above 630 mm²); the calculator keeps the half-size convention there, which exceeds that minimum. With aluminium actives Table 5.1 permits a smaller copper earth at the same active size. Table 5.1 is only the minimum — the earth still has to pass the adiabatic check I²t ≤ k²S² at both ends of the run and the Zs loop check, which the calculator runs automatically, upsizing the earth (never beyond the active size) if needed.
What is the smallest cable allowed under AS/NZS 3000?
- Minimum conductor sizes depend on the circuit type, conductor material, wiring system and mechanical protection. From AS/NZS 3000:2018 Table 3.3 and common Australian practice: lighting final subcircuits are typically 1.0 mm² copper minimum, and socket-outlet final subcircuits are typically 2.5 mm² copper minimum. Signal and relay control circuits can drop to 0.5 mm² and flexible cords to 0.75 mm²; aerial wiring is 6 mm² copper or 16 mm² aluminium. Submains and consumer mains are not in Table 3.3 — their size is driven by capacity, voltage drop, short-circuit withstand and Zs, but practical minimums still apply (consumer mains typically not less than 16 mm² copper or 25 mm² aluminium under most utility service rules). The calculator’s standard size set runs from 1 mm² to 630 mm² in the AS/NZS 3008 preferred series.
How do I size a cable for a three-phase motor?
- Take the motor full-load current from the nameplate (not the locked-rotor or starting current — protection device coordination handles those transients) and enter it into the Design Current field. For continuous-duty motors a common convention is to size on roughly 1.25 × FLA to allow for sustained running, but the actual design current depends on duty cycle, overload protection, starting method, installation conditions and the AS/NZS 3000 Section 4 motor requirements. Set Phases to 3 and Construction to 3C+E or 3x1C+E (no neutral for a balanced three-phase motor). Voltage drop on the longest motor run is usually the governing constraint, especially for soft-started or VFD-fed motors where excessive volt drop also worsens torque output and starting performance.
How do I handle parallel cable runs?
- Set the Parallel Runs stepper to the number of identical sets and the design current per run becomes Ib / n; the calculator picks a cable that, multiplied back by n, satisfies the loading. AS/NZS 3000 Cl. 3.4.3 (capacity) and Cl. 3.6.3 (voltage drop) require every run to be no smaller than 4 mm² and identical in length, cross-sectional area, conductor material and installation method, which ensures the current actually shares evenly. The earth conductor has its own parallel-runs stepper. Parallel single-core runs are usually grouped and may also need the grouping derating from AS/NZS 3008.1.1 Tables 3.33 to 3.43 — switch on Apply Derating and the calculator pulls the matching factor automatically.
Which MCB protective device curve should I use — B, C or D?
- The MCB curve sets the magnetic instantaneous trip threshold the calculator uses for its earth-fault loop impedance check. Curve B trips at 3–5× In and suits resistive loads and lighting. Curve C trips at 5–10× In and is the general-purpose default. Curve D trips at 10–20× In and is reserved for transformers, motors and other loads with high inrush that would nuisance-trip a C curve. The compliance trade-off comes through Ia in Zs ≤ U₀ / Ia: a higher curve raises Ia, which lowers the maximum permissible Zs and tightens the earth-fault loop impedance constraint. If a C-curve passes Zs and a D-curve does not, you usually need to drop a curve, increase the cable size to lower Zs, or switch to an electronic-trip device.
Does the calculator handle four-core cables and neutral derating?
- Yes. The Construction selector covers four single-phase layouts (2C+E, 2C, 2x1C+E, 2x1C) and six three-phase layouts (4C+E, 3C+E, 4C, 4x1C+E, 3x1C+E, 4x1C). For a balanced three-phase load with no neutral — most three-phase motors — pick a 3C+E or 3x1C+E construction; for any submain feeding single-phase loads downstream pick a 4C+E or 4x1C+E so a neutral is included. The calculator counts loaded conductors when it pulls the AS/NZS 3008.1.1 capacity table — three loaded actives in a 4C+E cable are rated lower than two loaded actives in a 2C+E. Where the load is harmonic-rich (LED lighting, drives, IT equipment), AS/NZS 3008.1.1 requires the neutral to be treated as a current-carrying conductor; keep a 4C construction and accept the four-loaded-conductor rating.
Is the ElecAS cable size calculator free?
- Yes — the AS/NZS 3008.1.1:2025 cable size calculator runs entirely in your browser, with no account required for the standard workflow, and the cable selection report exports as a PDF you can attach to the project documentation. Project metadata (project name, number, address, designer, revision) is captured at the top of the page and flows into the exported report so the PDF is ready to issue.